Pylontech A1000-OMNI: 500kW / 1,034.88kWh container ESS
- 1,034.88kWh reference energy
- 500kW reference conversion power
- Air-cooled container; IP54 reference

Customized C&I solution — price on request. Estimated lead time: approximately 90 days, subject to confirmation of the final configuration and delivery schedule.
A1000-OMNI — system overview
A1000-OMNI is an air-cooled container storage solution with a reference energy capacity of 1,034.88kWh and a 500kW PCS. It offers an integrated AC storage starting point for larger commercial loads, energy shifting and solar self-consumption projects.

Configuration and integration
The product family covers approximately 690–1,035kWh and 250–500kW. The reference PCS operates at 400V ±15%, and the battery voltage range is 638–781V DC. The enclosure dimensions are 2,991 × 2,438 × 2,896mm, with a published mass of 13 tonnes.
Application and project planning
Its smaller container footprint can be useful where a full 20-foot arrangement is unnecessary, but access, ventilation and lifting still require engineering. Compare the selected energy configuration with the actual duration of the evening load or scheduled discharge. Short-duration PCS overload is a timed limit rather than extra continuous capacity.
Configuration notes
The reference enclosure is IP54 and uses air cooling. The final quotation should identify the selected capacity, PCS rating, regional frequency configuration and auxiliary supply requirements.
Choosing and integrating Pylontech A1000-OMNI
A one-megawatt-hour-class option for business energy projects
A1000-OMNI pairs a 1,034.88kWh reference battery capacity with 500kW conversion power. This makes it a useful comparison point for commercial sites assessing container-scale storage rather than individual battery cabinets. The useful duty depends on the site demand and control strategy: shifting daytime solar energy, reducing selected demand peaks and supporting planned backup loads are distinct design objectives.
Consider the thermal environment and service arrangement
The reference platform uses air cooling and an IP54 enclosure. The location should therefore be assessed for ventilation, ambient conditions and maintenance access in line with the manufacturer installation requirements. A container positioned for convenient delivery may not be the best position for ongoing servicing or electrical connection. Review those practical requirements alongside the energy and power figures.
Specify what the microgrid must do
For an industrial microgrid, state how the storage should interact with the grid, existing PV and any generator. The presence of those components in a concept image does not establish an approved operating sequence. Controls, switching and communications must be designed around the actual equipment. Include the loads that cannot be interrupted, expected outage duration and available charging sources in the project brief.
Where A1000-OMNI fits in the energy system
The completed installation coordinates storage, power conversion and site distribution. The division between integrated equipment and external components depends on the selected model and project configuration.

Technical reference
Technical data
| General Data | |
|---|---|
| Dimension (W*D*H mm,w/o inverter) | 2991*2438*2896 |
| Weight (tons) | 13 |
| Working Temperature Range (℃) | -20~50* |
| Protection Class | IP54 |
| Humidity | 5%~95% |
| Fire extinguishing | Aerosol |
| Cooling System | Air Cooling |
| Cooling system consumption (kW, Cooling/Heating) | 15 |
| Aux. Power Consumption (kW, continuous/peak, incl. HVAC) | 16 |
| Anti-corrosion | C3H (C5 Optional) |
Technical data
| Battery Data | |
|---|---|
| System Capacity (kWh) | 1034.88 |
| Depth of Discharge | 98% (single string) |
| Cycle Life | >7000 |
| DC Voltage Range (Vdc) | 638~781 (single string) |
Technical data
| PCS DC/AC Data On-grid Mode | |
|---|---|
| Rated AC Power (kW) | 500 |
| Rated AC Output Voltage (Vac) | 400±15% |
| Rated AC Output Frequency (Hz) | 50/60±2.5 |
| Max AC Current (A) | 760 |
| Overload Capacity | 125%~150%@ 200ms |
| AC PF | 0.8~1 leading or lagging |
| CEC Efficiency | 97% |
| Isolation Type | Non isolated type |
Project scope and delivery
Send Solar Deity your load profile, required backup duration, PV capacity, site location and connection requirements. The quotation will define the selected equipment, control interfaces and commissioning scope. Civil works, transport, external switchgear, transformers and installation are included only where expressly listed in the project quotation. The approximately 90-day lead time is a planning estimate rather than a stocked-item dispatch promise.
Manufacturer documentation
Pylontech official product reference
Reference figures apply to the documented configuration and manufacturer test conditions. Confirm the final model revision and applicable regional approvals before procurement.
Monitoring and operational planning
For a A1000-OMNI project, define which site measurements, battery status information and alarms are required, who can access them, and how the chosen controls communicate. Gateways, software, network access and remote support should be stated in the quotation rather than assumed.

Pylontech A1000-OMNI datasheet and document downloads
Choose the relevant manufacturer document below. Each PDF is hosted on Solar Deity; the language and file size are shown before you open it.
Pylontech A1000-OMNI: frequently asked questions
Is the system exactly 1,000kWh?
The detailed reference capacity is 1,034.88kWh. The 1MWh description is a capacity-class shorthand, not a replacement for the technical table.
Does 500kW mean every load can be supported?
No. Load characteristics, starting peaks, power quality requirements and the final conversion arrangement must all be checked. The site connection and essential-load design also matter.
Can a generator be integrated automatically?
Generator integration requires a compatible control and switching arrangement. Provide the generator model and operating requirements so the proposal can address the complete system.
Is outdoor placement unrestricted because it is containerised?
No. The IP rating does not remove the need for suitable foundations, drainage, clearances and environmental assessment. The final installation must follow the manufacturer requirements and site design.
Where can I get the A1000-OMNI datasheet?
Use the document download cards above to open the matched PDF. Check the model, language and revision against the equipment being specified.
Compare the separate Pylontech A2000-OMNI reference — model scope and compatibility differ.
Request a project quotation for A1000-OMNI
Share your site requirements and the exact product configuration you are considering. Our C&I enquiry form accepts business details, electricity usage and project requirements.