Pylontech L3300-OMNI: 1,675kW / 3,344kWh container ESS
- 3,344kWh reference energy
- 1,675kW reference power
- 690V AC interface in the cited document

Customized C&I solution — price on request. Estimated lead time: approximately 90 days, subject to confirmation of the final configuration and delivery schedule.
L3300-OMNI — system overview
L3300-OMNI combines liquid-cooled battery storage and a PCS in a container solution. The EN-SD-260401 reference configuration lists 3,344kWh nominal battery capacity and 1,675kW rated AC power. This integrated AC solution is distinct from the L3300-BAT battery-only container.

Configuration and integration
The reference output is 690V, with 50/60Hz frequency and a 1,164–1,497V battery range. Published depth of discharge is 95% for a single string, and the PCS maximum efficiency is 98.5%. These component specifications should not be interpreted as guaranteed whole-project energy savings.
Application and project planning
The 690V interface is an important selection point for commercial and utility designs. The required transformer, switchgear and connection voltage should be defined before ordering. The container measures 6,058 × 2,438 × 2,896mm and has a published reference weight of 34 tonnes.
Configuration notes
The brochure headline describes broader family ranges, while this technical summary identifies the 1,675kW/3,344kWh reference configuration. Final dispatch limits and installation requirements follow the approved project design.
Choosing and integrating Pylontech L3300-OMNI
A defined power-and-energy reference for larger projects
The cited L3300-OMNI document pairs 3,344kWh with 1,675kW. This gives a more specific comparison basis than the 3.3MWh family label alone. A logistics or industrial project should still determine how much of that energy and power is useful for its operating schedule, and whether the proposed control strategy prioritises demand management, solar energy shifting or another defined duty.
A 690V interface requires a site-level connection design
The reference AC interface is 690V, which must be coordinated with the actual site distribution and any transformer arrangement. It should not be presented as a direct connection to an arbitrary commercial board. The integration proposal needs to identify conversion, protection, metering and connection responsibilities, and confirm the final equipment revision used for the design.
Compare the OMNI and BAT families correctly
The similarly named L3300-BAT page describes a separate battery-side product with a 3,347kWh reference. This OMNI page follows the 2026-04-01 document and its 3,344kWh value. Keeping those references separate prevents a comparison from mixing the capacity, voltage or equipment scope of different products. Ask for the exact model schedule when comparing supplier quotations.
Where L3300-OMNI fits in the energy system
The completed installation coordinates storage, power conversion and site distribution. The division between integrated equipment and external components depends on the selected model and project configuration.

Technical reference
Technical data
| General Data | |
|---|---|
| Dimension (W*D*H mm,w/o inverter) | 6058*2438*2896 |
| Weight (tons) | 34 |
| Working Temperature Range (℃) | -30~55 |
| Protection Class | IP55 (BOL) |
| Cooling System | Liquid Cooling |
| PCS DC/AC Data On-grid Mode | |
| Rated AC Power (kW) | 1675 |
| Max. Efficiency | 98.50% |
EN-SD-260401 reference battery and PCS
| Nominal capacity | 3344kWh |
|---|---|
| Battery type | Li-ion (LFP) |
| Continuous C-rate | 0.5C |
| Depth of discharge | 95% (single string) |
| Battery DC range | 1164–1497V |
| Rated AC voltage | 690V (−15% to +10%) |
| Frequency | 50/60Hz |
| Communication | RS485, Ethernet, CAN |
Project scope and delivery
Send Solar Deity your load profile, required backup duration, PV capacity, site location and connection requirements. The quotation will define the selected equipment, control interfaces and commissioning scope. Civil works, transport, external switchgear, transformers and installation are included only where expressly listed in the project quotation. The approximately 90-day lead time is a planning estimate rather than a stocked-item dispatch promise.
Manufacturer documentation
Pylontech official product reference
Reference figures apply to the documented configuration and manufacturer test conditions. Confirm the final model revision and applicable regional approvals before procurement.
Monitoring and operational planning
For a L3300-OMNI project, define which site measurements, battery status information and alarms are required, who can access them, and how the chosen controls communicate. Gateways, software, network access and remote support should be stated in the quotation rather than assumed.

Pylontech L3300-OMNI datasheet and document downloads
Choose the relevant manufacturer document below. Each PDF is hosted on Solar Deity; the language and file size are shown before you open it.
Pylontech L3300-OMNI: frequently asked questions
Why does this page say 3,344kWh rather than 3,347kWh?
The 3,344kWh figure belongs to the cited L3300-OMNI document. The 3,347kWh value on the L3300-BAT page refers to a different product configuration.
Can it connect directly to a standard 400V site?
Do not assume that. The cited interface is 690V; the project engineer must define the appropriate connection arrangement for the actual site.
Is the reference power available throughout every operating condition?
Manufacturer limits, battery condition, temperature, auxiliaries and control settings can affect operation. The final proposal should state the applicable continuous duty and design conditions.
What helps size a logistics-site installation?
Supply interval demand data, operating hours, PV production information and the desired discharge window. Identify any essential loads and required backup behaviour separately from tariff-management objectives.
Where can I get the L3300-OMNI datasheet?
Use the document download cards above to open the matched PDF. Check the model, language and revision against the equipment being specified.
Compare the separate Pylontech L3300-BAT reference — model scope and compatibility differ.
Request a project quotation for L3300-OMNI
Share your site requirements and the exact product configuration you are considering. Our C&I enquiry form accepts business details, electricity usage and project requirements.